Is the Kilma Futura dry underfloor radiant system suitable if the room to be heated borders a non-heated room?
The UNI EN 1264:2021 technical standard prescribes the minimum insulation values that the insulating panel of a radiant system must have, depending on where it is to be installed.
In the case of installation on flooring that borders a non-heated room, the minimum thermal resistance corresponds to a value of R=1.25 [m2K/W]; it will be sufficient to use our 48 mm thick panel to achieve this value. In this case, the total thickness of the system will be given by the 48 mm thickness plus the thickness of the flooring.