Alinox
Adjustable automatic filling unit to refill closed circuits
Series 46
Adjustable automatic filling unit to refill closed circuits, diaphragm operated with anti-water hammer function, complete with removable cartridge micro filter, built-in check valve and dial pressure gauge to view downstream pressure.
Nickel brass body. |
Stainless steel seal seats. |
Elastomer seals. |
Threaded connections FF UNI-EN-ISO 228. |
Nominal pressure 25 Bar |
Max upstream pressure 25 Bar |
Adjustable downstream pressure 0.8 ÷ 5.5 Bar |
Max operating temperature 80 °C |
Pressure gauge scale 0 ÷ 10 Bar |
Filtering grade 800 μm |
Download
Diaphragm operated filling unit - pn 25
Code | Measure | Model | Pack | Outer | Cat. | € |
00460400 | G 1/2" | Alinox | 1 | 6 | 07.01 | ||00460400_LastPrice|| |