Immersion bit thermostat, complete with thermometer conduit
Series 382
Dual immersion thermostat with thermometric conduit, including a manual reset locking thermostat and a regulation thermostat.
Operating range: Min. 0 - Max. 120°C |
Triggering tolerance: Min. T ±6°C – Max T ±4°C |
Triggering temperature (fixed setting): Min. 50 - Max. 120°C |
Fixed setting 100°C |
Triggering tolerance +0/-6°C |
Control head temperature limit 85°C |
Electrical protection rating IP43 |
Contact capacity 16(4)A 250V |
Download
Dual immersion thermostat
Code | Pack | Outer | Cat. | € |
03820002 | 1 | 1 | 60.01 | ||03820002_LastPrice|| |
Accessory for 3603 Series RBM instrument holder manifold